Schneider Automation Modicon Quantum Ethernet Uživatelská příručka Strana 283

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 900
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 282
Modbus Plus NOMs
35013379 02 October 2007 283
LED Indicators
and Descriptions
The following figure shows the Modbus Plus NOM LED indicators.
The following table shows the Modbus Plus NOM LED Descriptions.
LED Descriptions
LEDs Color Indication when On
Ready Green The module has passed power-up diagnostics.
Run Green Indicates that the unit is in kernel mode–should always be OFF
during normal operations.
Modbus Green Indicates communication is active on the single RS-232 serial port.
Modbus+ Green Indicates communication is active on the Modbus Plus port.
Error A Red There is an error condition on Cable A of a dual cable Modbus Plus
network (140NOM21200 only).
Error B Red There is an error condition on Cable B of a dual cable Modbus Plus
network (140NOM21200 only).
Ready
Error B
Modbus +
Error A
Run
Modbus
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Zobrazit stránku 282
1 2 ... 278 279 280 281 282 283 284 285 286 287 288 ... 899 900

Komentáře k této Příručce

Žádné komentáře