I/O Modules
35013379 02 October 2007 513
*A range warning is issued when a channel input exceeds the rated input value. An
out-of-range bit is set when a channel input exceeds the rated input value by 2.34%
or when a broken wire is sensed on the channel. The warning bit is cleared when
the out-of-range bit is set.
I/O Map Status
Byte
The I/O map status byte is used by the 140ARI03010 Input module as follows:
Modsoft Module
Zoom Selections
Push <Enter> to display and select the overall module and channel configuration.
Note: The data format is 16-bit integer values in the positive range and an integer
value with the MSB indicating a negative sign in the negative range.
Channel 1 out of range or short circuit
12345678
MSB LSB
Channel 2 out of range or short circuit
Channel 3 out of range or short circuit
Channel 4 out of range or short circuit
Channel 5 out of range or short circuit
Channel 6 out of range or short circuit
Channel 7 out of range or short circuit
Channel 8 out of range or short circuit
1.0 DEG
0.1 DEG
CELSIUS
FAHRENHEIT
TEMPERATURE
RAW VALUE
Resolution:
Output unit:
Value Type: