35013379 02 October 2007 865
F
Error Stopped Codes
Error Stopped Codes
Overview The following is a list of error stopped codes and their definitions.
Error Stopped
Codes
The following is a list of error stopped codes for the Quantum system.
Stop Bit
Code (hex) Description
7FFF PLC unhealthy
8000 PLC stopped
4000 Bad I/O map
2000 PLC unconfigured
1000 Bad Modbus port intervention
0800 Bad segment scheduler
0400 Start-of-network (SON) did not start a segment
0200 Bad power-down checksum
0100 No end of logic detected
0080 Watchdog timer has expired
0040 Real time clock has failed
0020 Bad coil used table
0010 RIO option has failed
0008 Illegal node type found
0004 User logic checksum error
0002 Discrete disable table error
0001 Bad configuration
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com