706
35013379 02 October 2007
140DVO85300 I/O Verified 10-30 VDC Out Module
Overview The Quantum Verified Output module is a 10 ... 30 Vdc, 32 point output module with
diagnostic capability. The module will detect and report the output state sensed at
the field connector and, depending on the selected configuration, will verify that the
output point is in the state commanded by the PLC. The module is configured in four
groups of eight source outputs.
Specifications Key specifications for the Quantum 140DVO85300 module are as follows:
Specifications
Number of Output Points 32 in four 8 point groups
LEDs Active (Green): Bus communication present.
1 ... 32 (Green): Indicates output point status.
F (Red): Indicates incorrect output state on a channel,
loss of field power, or blown fuse.
Required addressing 2 words in, 2 words out
Voltage
Operating 10.0 ... 30 Vdc
Absolute Maximum 50 Vdc for 1.0 ms decaying voltage pulse
On state Drop/Point 0.4 Vdc @ 0.5 A
Maximum Load Current
Each Point 0.5 A
Each Group 4 A
Per Module 16 A
Off State Leakage/Point 0.4 mA @ 30 Vdc
Surge Current Maximum
Each Point 2.5 A @ 1 ms duration (no more than 6 per minute)
Response ( Resistive Loads)
OFF - ON 1 ms (typical), 2 ms (max)
ON - OFF 1 ms (typical), 2 ms (max)
Load Inductance Maximum 0.5 Henry @ 4 Hz switching frequency, or:
where:
L = Load inductance
I = Load current (A)
F = Switching frequency (Hz)
L =
0.5
I
2
F
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com